Protectowire 2000 FireSystem User Manual

Browse online or download User Manual for Security access control systems Protectowire 2000 FireSystem. FireSystem 2000 product data sheet. [en] [es] [fr] [pt]

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
FS2028 7
1
2 28 zones
FS2030 8 30 zones
FS2032 8
1
2 32 zones
FS2034 9 34 zones
Add
1
2 module space for each additional 2 zones.
Step 2 Select option code letter(s) from the “System Configuration
Guidesection of this catalog sheet and show quantity when
necessary. Note options which require enclosure module
space(s).
Step 3 To determine the proper size system enclosure, add
the module spaces required for the basic control unit
(Step 1) plus the module spaces required for the quantity
of each option selected (Step 2). If the total module spaces
required for the system exceed the size of the largest enclo-
sure, a second extender enclosure will be required. Select
two enclosures whose total module capacity equals or
exceeds that required for the complete system.
Step 4 Finalize complete system model number as shown in
the System Configuration Guide, Section D.
Step 5 Each 2000 Series Control Panel is custom assembled and
tested at the factory as a complete system. In order to
ensure conformance with each customers operational
requirements, every order should be accompanied by a brief
description of the panels operating logic and zone func-
tions.
System Configuration Guide
A. Model number of basic system control unit selected in Step 1.
Specify AC input voltage: 120 or 240VAC
Specify battery charger adjustment code: GC Gel Cell (Std.)
NC Nickel
Cadmium
B.
Options Encl. mod.
space
A–Protectowire alarm point location meter
PDM–1000–2
C116 zone alarm scanner
C2 1 32 zone alarm scanner RequiresOption A
C3 1 48 zone alarm scanner
D
1
2 Water flow detection zones (2/card)
E
1
2 Switch supervisory circuits Class A/B
(2 circuits/module)
F
1
2 Solenoid release and initiating device module
(1 release and 1 Class B initiating circuit/module)
H–Intrinsic safety barrier for Class B, 2-wire
(1-2) 0 detection circuits
(3-16) 1 (Option not available with system
(17-32) 2 ground fault detection)
Determine module space based upon zone
qty. shown in brackets.
K–Dual Channel DC Isolator for two (2) Class
B, 2-wire detection circuits (Not compatible
with Option A)*
L–Auxiliary output relay – SPDT
LL Auxiliary output relay – DPDT
P–Battery charging meters
Q Time delay relay
R–Auxiliary common alarm relay – DPDT
RR Auxiliary relay module – 8-SPDT relays
(1 amp @ 24
VDC)
S–Auxiliary common trouble relay – DPDT
T–Class A (NFPA Styles X & Z) audible
circuits (main panel, general alarm only)
U
1
2 Audible expander card (I circuit, Class A or B)
V–Zone voting module
W–PS–2 auxiliary power supply
Y–PS–95 power conditioning module
Z Door mounted, key operated, control switches
(reset, alarm silence, trouble/supervisory
silence & lamp test)
C. Enclosures
EN2 Commercial Type NEMA 1 2 module enclosure
EN4 Commercial Type NEMA 1 4 module enclosure
EN6 Commercial Type NEMA 1 6 module enclosure
EN9 Commercial Type NEMA 1 9 module enclosure
EN12 Commercial Type NEMA 1 12 module enclosure
LTi2X Industrial Type NEMA 4X 2 module enclosure
LTi4 Industrial Type NEMA 4/12 4 module enclosure
LTi6 Industrial Type NEMA 4/12 6 module enclosure
LTi9 Industrial Type NEMA 4/12 9 module enclosure
D. Example of complete system model number. Note that the
quantity of each option ordered is shown after its Option Code
Letter.
FS2004-120-GC-F2-EN6
Control panel with four 2–wire detection zones operating on
120VAC 50–60Hz input & gel cell battery backup; (2) solenoid
release and initiating device modules (1 release & 1 Class B initi-
ating circuit/module); all in a six (6) module beige enclosure.
Not all options are both UL Listed and FM Approved.
Consult factory for details.
Features
Easily expandable. All new plug-in board design
Two supervised audible circuits
Lamp and system trouble circuit test
Ground fault detection
LTi Series NEMA 4/12 enclosures available
Monitors up to 5,000 feet (1,524m) of Protectowire
Linear Heat Detector per zone
Up to 30 smoke detectors per zone
Description
The FireSystem 2000 is a fully supervised, non-coded fire alarm
control panel available in multiple zone configurations. The
control panels are modular in design and feature individual con-
trol modules designed to meet specialized system requirements
for commercial, institutional, and light industrial applications.
The system is both UL listed and FM approved and conforms to
applicable NFPA 72 requirements for local and auxiliary protec-
tive signaling systems. It may also be used as part of a propri-
etary fire alarm system or, when properly configured, is capable
of sprinkler supervisory service, water flow alarm, preaction
sprinkler or deluge system release.
The basic 2-wire system control panel and its associated power
supply provide the following standard features: two (2) super-
vised detection circuits, that may be field wired for either Class
A (Style D) or Class B (Style B); two (2) supervised Class B
(Styles W & Y) audible appliance circuits; battery charger and
monitor; ground fault detection; lamp test; one (1) set of SPDT
common alarm contacts, two (2) sets of Form A or B (selectable)
common trouble contacts, and one (1) set of Form A or B
(selectable) common supervisory contacts. Common trouble
contacts may be programmed for silenceable or non-silenceable
operation.
FireSystem 2000
Commercial and Light Industrial
Fire Alarm Control Panel
DS 9004N-0315 (1C)
APPROVED
© 2009 The Protectowire Co., Inc.
An ISO 9001:2008 Registered Company
The Protectowire Company, Inc.
n
60 Washington Street, Pembroke, MA 02359 U.S.A.
n
p:781-826-3878
n
f:781-826-2045
web: www.protectowire.com
n
email: pwire@protectowire.com
SPECIAL HAZARD FIRE DETECTION SYSTEMS
* Size restrictions limit use of Option K to LTi Systems only.
Protectowire Total System Capability
Now it is easier than ever to specify a complete Protectowire System with all of its unique features and reputation for
reliability. The Protectowire Company offers an extensive line of fire and heat detection sensors and related products,
including:
• Optical Flame Detectors
• Manual Pull Stations
• Smoke Detectors
• Heavy-Duty Alarm Bells
• Horns
Visual Signals/Strobes
All Protectowire products have been specifically designed and tested for compatibility and reliable operation with
Protectowire Control Panels.
Contact your local authorized Protectowire distributor for help in planning the system best suited to your needs.
Page view 0
1 2 3 4 5 6

Summary of Contents

Page 1 - Fire Alarm Control Panel

FS2028 71⁄2 28 zonesFS2030 8 30 zonesFS2032 81⁄2 32 zonesFS2034 9 34 zonesAdd 1⁄2 module space for each additional 2 zones.Step 2 Select option code l

Page 2

FlexibilityThe basic 2000 Series Control Panel is designed for easy expansion ofsystem capability by adding additional modules and functions to thesta

Page 3

FlexibilityThe basic 2000 Series Control Panel is designed for easy expansion ofsystem capability by adding additional modules and functions to thesta

Page 4

FlexibilityThe basic 2000 Series Control Panel is designed for easy expansion ofsystem capability by adding additional modules and functions to thesta

Page 5

FS2028 71⁄2 28 zonesFS2030 8 30 zonesFS2032 81⁄2 32 zonesFS2034 9 34 zonesAdd 1⁄2 module space for each additional 2 zones.Step 2 Select option code l

Page 6

FS2028 71⁄2 28 zonesFS2030 8 30 zonesFS2032 81⁄2 32 zonesFS2034 9 34 zonesAdd 1⁄2 module space for each additional 2 zones.Step 2 Select option code l